3D FIRE DETECTOR MAPPING



HAZARD SCENARIO IDENTIFICATION - 3D CAD MODEL DEVELOPMENT



Hazardous Scenarios are identified based on P&I Diagrams and leak points are selected. Cad models in 3D are developed from 2D Plot Plans / Elevation drawings and Pipe routing drawings. If a 3D Cad model is available, it is imported into our 3D Fire and Gas Detector Mappings Application.





PROCESS PLANT SECTION



CONSEQUENCE MODELING



Thermal Radiation Contours recommended per ISA TR 84.00.07 (2018) and Flame Shape are simulated using DNV GL Phast Software. The 3D Radiation Contours are generated from DNV GL radiation report using our advanced 3D Cad Fire and Gas Application.



jet fire radiation footprint 5 kw/m2 dnv-gl phast



jet fire 3d RADIATION FOOTPRINT 5 KW/M2



JET FIRE 3D RADIATION CONTOURS 5 KW/M2



JET FIRE RADIATION FOOTPRINT 5/12.5/37.5 KW/M2 DNV-GL PHAST



JET FIRE 3D RADIATION/FLAME FOOTPTRINT 5/12.5/37.5 KW/M2



JET FIRE RADIATION SIDE VIEW 5/12.5/37.5 KW/M2 DNV-GL PHAST



JET FIRE 3D RADIATION/FLAME SIDE VIEW 5/12.5/37.5 KW/M2



JET FIRE FREQUENCY RADIATION ISO-CONTOURS



Jet Fire Radiation Frequency ISO-Contours at different elevations are evaluated in our 3D Fire and Gas Detector Application. A grid of 0.1x0.1 meter is utilized.



Jet Fire Radiation Iso - Contours 5 kw/m2 . height - 2.35 meters



FIRE ZONE 3D GRADING - FIRE DETECTOR PLACEMENT



Fire detection performance targets are evaluated per ISA TR 84.00.07 (2018) and The Grade Zone is assigned accordingly. Using our 3D CAD Fire and Gas Application, the 3D Grade Zone is defined from the outer equipment surface in the Fire Zone. Fire Detector ‘s 3D CAD Field of View is implemented per its ANSI/FM 3260 Approval test report and it is scale to meet the Radiant Heat Output (RHO) of the required design fire to be detected.



FIRE ZONE GRADING - FIRE DETECTOR LAYOUT



3D FIRE DETECTOR COVERAGE



Having defined the Fire Zone, the 3D Grade Zone and the position the Fire detector ‘s 3D Field of View, the 3D Fire Detector Coverage is evaluated with our advanced 3D Fire and Gas Detector Mapping Application.

For each Fire Detector, the Fire Detector's Unobstructed View is determined by projecting the Fire Detector’s Obstructed Field of View within the 3D Grade Zone and subtracting it from the Fire Detector's Field of View. The 3D Fire Detector Coverage is the fraction of the 3D Grade Zone covered by the Fire Detector ‘s 3D Unobstructed Field of View.

For a One out of N Voting (1ooN), the 3D Fire Zone Detector Coverage is the fraction of the 3D Grade Zone covered by the combined N Fire detector ‘s 3D Unobstructed Field of View. For N out of N Voting (NooN), the 3D Fire Zone Detector Coverage is the fraction of the 3D Grade Zone covered by the intersection of N Fire detector ‘s 3D Unobstructed Field of View. Undetected 3D Coverage (0ooN) as well as Detected 3D Coverage (1ooN / NooN) are clearly presented in the 3D Cad model of the Process Plant.




1oo3 Voting



3oo3 Voting



1oo2 Voting



2oo2 Voting